GDYD-2030A 30kVA.200kV Atomatik AC/DC Hipot Gwajin Saitin
●7inch launi LCD allon, tare da PLC sarrafa kansa.
●HV Voltage, LV ƙarfin lantarki, LC halin yanzu auna a lokaci guda, tare da babban madaidaicin firikwensin da guntu tarin ayyuka mai girma.
●Yanayin atomatik da yanayin jagora don zaɓi.
●Nuna ƙarfin lantarki na HV, ƙarfin lantarki na LV, LV na yanzu, lokaci, da sakamako mai tsayi.
●Ƙarfin wutar lantarki da kariya na yau da kullum.Za'a iya saita ƙarfin wutar lantarki, HV na yanzu babba, LV na yanzu babba da lokaci.
●Sifili-fara aikin.Ana iya ci gaba da gwajin bayan wutar lantarki ta koma sifili.
●Ajiye bayanai har zuwa 8000pcs a cikin watanni 3.Yana da tashar USB don loda bayanai zuwa faifan USB.
●Lokacin saita ƙarfin lantarki ya isa, zai zama lokaci ta atomatik.Bayan lokaci, ƙarfin lantarki zai koma sifili.
●Lokacin da halin yanzu LV ya ƙare ƙimar saiti, za a yanke wutar lantarki ta atomatik kuma zai koma sifili.Lokacin da HV halin yanzu ya wuce saitin ƙima, za a yanke abin gwajin kuma ana iya ci gaba da gwaji.
●Tare da ikon hana tsangwama, dacewa da yanayin lantarki.
●Tare da ƙafafun duka naúrar sarrafawa da naúrar HV, mai sauƙin motsawa.
Ƙayyadaddun naúrar sarrafawa
●Wutar lantarki: AC380V, 50/60Hz
●Yawan aiki: 30kVA
●Wutar lantarki mai fitarwa: AC 0-430V
●Ƙididdigar fitarwa na yanzu: 75A
●Ƙididdigar kewayon gyara na yanzu: 0-75A
●HV voltmeter kewayon: 0-200kV
●Daidaito: 1.5% na karatun ± 1 lambobi (FS)
●HV ammeter kewayon: 0-100mA
●Daidaito: 1.5% na karatun ± 1 lambobi (FS)
●LV ammeter kewayon: 0-25A
●Daidaito: 2.0% na karatun ± 1 lambobi (FS)
●Tsawon lokaci: 1s-99h
●Nauyi: kimanin 116kg
●Girma: 520mm (L)*460mm (W)*1140mm (H)
Gwajin wutan lantarki (HV unit) ƙayyadaddun bayanai
●Input irin ƙarfin lantarki: 0-400V
●Shigarwa na yanzu: AC 0-75A
●Wutar lantarki mai fitarwa: AC 0-200kV, DC 0-200kV
●Fitarwa na yanzu: AC 150mA, DC 106mA
●Yawan aiki: 30kVA
●Juyin Juyi na gefen HV/LV: 500:1
●Aunawa ƙarfin lantarki: AC 0-100V
●Daidaito: 1.5% na lambobi ± 1 (FS)
●Babu kaya na yanzu: <10%
●Wutar lantarki: <10%
●Nauyi: kimanin 180kg
●Girma: 630mm(D)*1730mm(H)
Yanayin aiki
●Wurin aiki: Babu iskar gas, tururi, ƙurar sinadari da fashewa da matsakaicin lalata wanda zai yi tasiri ga rufi.
●Yanayin yanayi: -20--50 ℃.
●Zafin muhalli: ≤85% RH (babu condensing).