Transformer na yanzu (CT) wani muhimmin kayan lantarki ne a cikin tsarin wutar lantarki.Yana da alhakin keɓancewa tsakanin manyan tsarin wutar lantarki da ƙananan ƙarfin lantarki da jujjuya babban ƙarfin lantarki zuwa ƙananan ƙarfin lantarki.Ko wayoyi daidai ko a'a yana da mahimmanci ga aikin yau da kullun na karewa, ma'auni, ma'auni da sauran kayan aikin tsarin.Lokacin da aka shigar da sabon CT kuma an saka kebul na biyu na CT aiki ko maye gurbinsa, auna daidaiton polarity na CT ya rigaya ya zama muhimmiyar hanyar aiki don ma'aikatan kariyar relay.Na gaba, HV Hipot zai gabatar da ma'aunin polarity na CT daki-daki:

HV Hipot GDHG-201A na'ura mai ba da hanya tsakanin hanyoyin sadarwa na CT/PT
1. Menene polarity na CT?
Polarity shine ƙarfin lantarki wanda babban coil na farko da coil na biyu ke haifar da shi ƙarƙashin aikin magnetic flux iri ɗaya na tushen ƙarfe.Ƙarshen biyun da suka kai matsayi mai girma a lokaci guda ko kuma ƙarshen da ke da ƙananan ƙarfin lokaci guda ana kiransa ƙarshen polarity iri ɗaya.
Abin da ake kira na'ura mai canzawa (CT) polarity yana nufin alakar da ke tsakanin shugabanci na yanzu tsakanin iska ta farko da na biyu.Dangane da ka'idoji, ƙarshen farko na iskar CT na farko ana yiwa alama P1, kuma ƙarshen wutsiya alama ce ta P2;ƙarshen kai na iskar na biyu ana yiwa alama S1, kuma ƙarshen wutsiya ana yiwa alama S2.A cikin wayoyi, P1 da S1, P2 da S2 ana kiran su ƙarshen polarity iri ɗaya.Tsammanin cewa I1 na yanzu na iska na farko yana gudana daga ƙarshen kai P1 kuma yana fitowa daga ƙarshen wutsiya P2, I2 da aka haifar a cikin iska na biyu yana fitowa daga ƙarshen kai S1 kuma yana gudana daga ƙarshen wutsiya S2.A wannan lokacin, motsin maganadisu da aka haifar a cikin tsakiyar ƙarfe A cikin wannan jagorar, irin wannan alamar polarity na CT ana kiranta depolarization.Akasin haka, ana kiran shi ƙara polarity.Masu taswirar da aka saba amfani da su na yanzu, sai dai in an kayyade, yi amfani da depolarization.
2. Me yasa auna polarity na CT?
Dole ne a gwada polarity na taransfoma na yanzu kafin da bayan mikawa da sake gyarawa.Bugu da kari, lokacin da bambancin kariyar ke aiki, rashin aikin kariyar wutar lantarki ko mitar sa'a watt ya koma baya, dole ne a duba polarity na CT.Domin idan an haɗa polarity na na'ura mai ba da hanya tsakanin hanyoyin sadarwa ba daidai ba a lokacin wayoyi, haɗari masu zuwa zasu faru:
(1) Idan aka yi amfani da na’urar taransifoma na yanzu a cikin da’irar kariyar relay, hakan zai sa na’urar kariya ta na’urar ta lalace ko kuma ta ki yin aiki, sannan kuma hakan zai yi tasiri wajen sa ido da sarrafa na’urar wutar lantarki, har ma da jefa kayan aiki da amincin mutum cikin haɗari a lokuta masu tsanani.
(2) Idan aka yi amfani da na'urar taransifoma na yanzu a cikin da'irar ma'aunin kayan aiki, zai sanya alamar kayan aiki da mita daban-daban da ma'aunin makamashin lantarki ba daidai ba.
(3) Idan aka yi amfani da na'urar tauraro na yanzu tare da haɗin tauraron da bai cika ba, idan aka juya polarity na kowane lokaci, halin yanzu na lokaci ɗaya (yawanci matsakaicin lokaci) na injin da ba a haɗa shi ba zai ninka sau da yawa fiye da na sauran matakan.
(4) Idan aka yi amfani da na'urar tauraro na yanzu tare da haɗin tauraron da bai cika ba, idan an juyar da matakan biyu, kodayake yanayin halin yanzu a gefen sakandare na iya ci gaba da daidaitawa, bambancin kusurwa na lokaci tare da daidaitaccen gefen halin yanzu shine 180 °, don haka zai juya mita.
Saboda haka, yana da matukar muhimmanci a yi hukunci daidai ko polarity na na'ura mai ba da hanya tsakanin hanyoyin sadarwa daidai ne ko a'a.