A watan Agusta, masu fasahar HV Hipot sun tafi Xiangyang bayan-tallace-tallace.Manufar wannan tafiya ita ce samar da sabis na lalata wutar lantarki ga Kamfanin Samar da Wutar Lantarki na Xiangyang.
Bayan isa wurin, tare da taimako da haɗin gwiwar abokin ciniki, za a aiwatar da shigar da janareta na wutar lantarki na walƙiya.

Gyaran kan-site na GDCY-400kV walƙiya ingiza wutar lantarki janareta
Daidaita nisan ƙwallon ƙafa a kan-site: daidaitawar nesa ta ƙwallon jiki da ƙirar ƙwallon ƙwallon ƙwallon ƙwallon (3000/200/aunawa)


Gwajin Gudun-in-site: 30KV tabbatacce da ƙarancin gwaje-gwaje masu yawa na polarity (haɗu da T1 = 1.2 ± 30% / T2 = 50 ± 20% us / TC = 2 zuwa 6us)


Gwajin ƙarfin kan-site: ƙimar ƙarfin lantarki 80% fitarwa


Horarwar ka'idar da aiki a kan wurin:
Ayyukan abokin ciniki - gwajin samfurin gwaji na kwaikwaya: 10KV wutar lantarki
1. Cikakken gwajin igiyar ruwa


Bukatun gwaji: gwajin ƙarfin lantarki 75KV, lokacin ƙawancen lokaci T1 = 1.2 ± 30% / T2 = 50 ± 20% mu
Aikin filin: ta amfani da fitowar wutar lantarki mai mataki biyu
Motsin motsin kan-site:
Juriya na kai: 150Ω don matakin farko, 500Ω don matakin na biyu (2 1KΩ a layi daya)
Wave wutsiya juriya: 1st mataki 45Ω, 2nd mataki 45Ω
Gwajin aiki da tsarin igiyar ruwa:
2. Gwajin yankewa


Bukatun gwajin: gwajin ƙarfin lantarki 85KV, lokacin kai T1 = 1.2 ± 30%, lokacin yankewa TC = 2 zuwa 6us
Aikin filin: ta amfani da fitowar wutar lantarki mai mataki biyu
Motsin motsin kan-site:
Juriya na kai: Level 1 75Ω, Level 2 500Ω (2 1KΩ a layi daya)
Wave wutsiya juriya: 1st mataki 45Ω, 2nd mataki 45Ω
Gwajin aiki da tsarin igiyar ruwa:
Bayan wannan jerin horo, abokin ciniki yana da zurfin fahimtar dukkanin kayan aiki, wanda ya sa abokin ciniki ya fi ƙarfin gaske a cikin ainihin aiki!