Tsare-tsare don Tsarin Gwajin Resonance Series
1. A lokacin gwajin, an haɗa lokacin gwajin zuwa babban ma'aunin wutar lantarki, kuma babban igiyar wutar lantarki yana buƙatar yin amfani da waya ta musamman maras kyau, kuma lokacin da ba a gwada shi ba yana ƙasa tare da harsashi na GIS;
2. Gwajin dole ne ya tabbatar da cewa gas na SF6 a cikin kowane ɗakin gas yana ƙarƙashin matsin lamba, kuma abun ciki na gas yana cikin kewayon da aka yarda da shi bayan sa'o'i 4 na hauhawar farashin kaya, kuma GIS yana cikin yanayin aiki.Za a iya yin gwajin bayan tabbatarwa;
3. Kafin matsawa gwajin, tabbatar da cewa an cire wutar lantarki a cikin GIS (idan GIS manufacturer ya yarda, za a iya matsawa da ƙarfin lantarki tare, amma gwajin resonant mita dole ne mafi girma fiye da 100Hz), da CT sakandare gajeren kewaye. kuma ya kamata a katse haɗin mai kama;

GDTF jerin tashar mitar jujjuyawar juzu'i tsarin gwaji
4. Ana ƙara ƙarfin gwajin gwajin zuwa bushing fitarwa, bushing core an haɗa zuwa babban ƙarfin wutar lantarki, kuma bushing karfe yana haɗa da waya ta ƙasa ta musamman na tsarin;
5. A lokacin gwajin, dole ne a yi amfani da wayoyi na musamman na ƙasa tsakanin sassan tsarin gwajin da kuma tsakanin tsarin gwajin da harsashi na GIS, kuma ba dole ba ne a yi amfani da sandar ƙasa a kan wurin don maye gurbin haɗin haɗin ƙasa tsakanin tsarin gwajin. da harsashi GIS;
6. Kula da ma'auni guda ɗaya tsakanin tsarin gwajin da grid ɗin wutar lantarki a kan yanar gizo, kuma dole ne a kasance wurin ƙaddamarwa akan layin haɗin tsakanin mai rarraba wutar lantarki da abin gwajin;
Ka'ida da al'amuran da ke buƙatar kulawar gwajin aikace-aikacen transfoma na waje
Gwajin da aka yi amfani da shi a waje shine gwaji na asali don gwada babban rufin na'urar, kuma mitar gwajin kada ta kasance ƙasa da 80% na mitar da aka ƙididdigewa;
Hankali ga gwajin aikace-aikacen waje na taransifoma:
1. Dukan iskar da aka gwada da kuma wanda ba a gwada ba ba su da ɗan gajeren kewayawa, kuma ba a yi amfani da iska ba bayan ɗan gajeren kewayawa.A ka'ida, samfurin gwajin dole ne ya kasance ba shi da yuwuwar dakatarwa;
2. A yayin gwajin, haɗin kai tsakanin tsarin jujjuyawar mitar mitar da harsashi da aka gwada yana ɗaukar waya ta ƙasa ta musamman da kamfanin ya samar;