GDKC-12A (GDKC-12B) (GDKC-13A) Analyzer Breaker Circuit
Babban ƙarfin wutar lantarki yana ɗaya daga cikin mahimman kayan sarrafawa a cikin tsarin wutar lantarki.Ana amfani da GDKC-12A/B (GDKC-13A) don gwada halaye masu ƙarfi na na'urar bugun wutar lantarki mai ƙarfi.Yana da sauƙi don aiki, tare da babban daidaito.
●Lokaci: buɗe/lokacin rufewa, a cikin aiki tare na zamani, aiki tare na lokaci-zuwa-lokaci na lambobin sadarwa 12.
●Rufe resistor: pre-canja lokaci, pre-switching waveform da juriya na rufe resistor na 6 tashoshi.
●Sake rufewa: buɗe-buɗe, buɗe-ƙusa, buɗe-kusa-buɗe lokaci ga kowace lamba.
●Bounce: rufe lokacin billa, lokuta, tsari da sigar kalaman kowane lambobi.
●Gudun gudu: saurin buɗaɗɗen lamba ko kusa, matsakaicin saurin gudu, yanayin yanayin tafiyar lokaci;na farko bude, na farko kusa da na biyu bude gudun sakewa.
●Tafiya: jimlar tafiya, buɗaɗɗen balaguro, kan tafiye-tafiye, wuce gona da iri, girman girman billa.
●Yanzu: Buɗe/rufe halin yanzu, zane na halin yanzu na maɗaurin buɗaɗɗe/kusa.
●Wutar lantarki: ginanniyar DC30 ~ 300V/20A dijital, daidaitacce tushen wutar lantarki, kammala gwajin aikin LV ta atomatik na mai watsewar kewayawa da auna ƙimar ƙarfin lantarki na mai watsewar kewaye.
●IPC ga mai watsa shiri.
●Ya dace don gwada ma'auni na kowane nau'i na SF6 na'ura mai kwakwalwa, GIS haɗin kayan aiki na lantarki, injin da'ira, mai keɓaɓɓen mai.
●Ƙarfin ƙarfin hana tsangwama.Hakanan yana iya gwadawa cikin sauƙi da auna daidai ko da interbus yana rayuwa a cikin tashar 500kV.
●Tare da firikwensin saurin duniya (na zaɓi), firikwensin saurin madaidaiciya, firikwensin juyawa, mai sauƙin shigarwa.
●Aiki sau ɗaya kawai don samun duk bayanai da sigar ƙaƙƙarfan ƙaƙƙarfan gwajin injin karya.
●Bayanan gwaji na ajiya na ƙungiyoyi 1000, ginanniyar agogo na ainihi, wanda ya dace don adana kwanan wata da lokacin gwaji.
●Nunin allo na LCD, tare da daidaitawar daidaitawa da ƙwaƙwalwar kashe wuta.
●Buit-in printer, don samun duk bayanai da zane a kowane lokaci cikin sauri.
●Tare da software mai sarrafa bayanan bayanan da'ira.Ana iya sadarwa tare da PC.Ana adana sakamakon gwajin kai tsaye a cikin rumbun kwamfyuta, kuma suna iya fitarwa zuwa nau'ikan nau'ikan allura daban-daban, na'urorin laser ko inkjet don buga rahotannin gwaji, don yin gwajin filin zuwa kwamfuta.
●Amfani da faifan U don adanawa da canja wurin bayanai kai tsaye.
●An haɗa software ɗin bincike mai dacewa bisa ga ma'anar buɗewa, saurin rufewa.Ya dace da ma'aunin sauri don kowane nau'in sauyawa.
●Muhallin Amfani
Ƙarfin shigarwa: 220V± 10%, 50Hz±10% / GDKC-12B: 230V± 10%, 60Hz±10%
Hawan iska: 86-106kpa
Zazzabi: -10-40 ℃
Danshi: ≤80% RH
●Ayyukan Tsaro
Resistance Insulation>2MΩ
Ƙarfin Dielectric: Shell na iya jure wa mitar ƙarfin wutar lantarki 1.5kV a cikin minti 1 ba tare da walƙiya da harbi ba.
●Ma'auni na asali
a.Lokaci: Range 20000.0ms ƙuduri 0.01ms
Kuskure 0.1ms ± 1 lambobi a cikin 2000ms
1ms± 1 lambobi a cikin 20000ms
Saukewa: GDKC-12B Ma'auni na asali
a.Lokaci: Range 20000.0ms ƙuduri 0.01ms
Kuskure 0.01ms ± 2 lambobi a cikin 250ms
0.1ms ± 2 lambobi a cikin 2500ms
1ms± 2 lambobi a cikin 20000ms
GDKC-13A Analyzer Mai Rarraba SaƙonniMa'auni na asali
Lokaci: Range 4000.0+6000.0 ms ƙuduri 0.1ms
Kuskure 0.1ms ± 1 lambobi a cikin 100ms
0.1% ± 1 lambobi fiye da 100ms
Lokaci guda
b.Gudun gudu: Rage 20.00m/s ƙuduri 0.01m/s
Kuskure ± 0.1m/s ± 1 lambobi tsakanin 0-2m/s
± 0.2m/s ± 1 lamba sama da 2m/s (± 0.2m/s ± 1ladi fiye da 100ms)
c.Tafiya:
| Nau'ukan | Rage | Ƙaddamarwa | Kuskure |
| Mai karyawa | 50.0mm | 0.1mm | 0.1±1lamba |
| Saukewa: SF6 | 300.0mm | 1 mm | |
| Maimai jujjuyawa | 600.0mm |
d.A halin yanzu: kewayon 20.00A ƙuduri 0.01A
e.Ƙarfin fitarwa: DC0-300V dijital daidaitacce / 20A (aikin nan take), ƙuduri 1V.
f.Girma: 360mm (L)* 280mm (W)* 300mm (H)
g.Nauyi: 10kg (9kg)
h.Nauyin GDKC-13A: 9kg