Mafi girman ƙarfin ƙarfin samfurin da aka gwada da kuma ɗigogi na reactance na na'urar gwajin gwaji, mafi ƙaranci tasirin ƙarfin ƙarfin.Don haka, lokacin da muke gudanar da gwajin ƙarfin ƙarfin AC na jerin resonance babban ƙarfin gwajin abu, ana buƙatar kai tsaye a auna ƙarfin lantarki a ƙarshen abin gwajin don hana abin gwajin fuskantar matsanancin ƙarfin lantarki.
HV Hipot GDTF-800kVA/400kV AC Resonant Test System
Lamarin da ya wuce kima na na'urar gwajin resonance na jerin abubuwan yana faruwa ne ta abubuwa masu zuwa:
(1) Na farko ana matsawa ba zato ba tsammani a maimakon ƙarawa a hankali daga sifirin ƙarfin lantarki.
(2) Lokacin da akwai ƙarin ƙarfin lantarki, ba zato ba tsammani ka yanke wutar lantarki, maimakon a faɗi daidai gwargwado zuwa sifili sannan a yanke wutar lantarki.Ana iya gani daga tsarin canji na iska mai canzawa cewa yanayi biyu na sama zai haifar da wuce gona da iri akan samfurin da aka gwada, wanda ba a yarda da shi ba.
Don (1) toshewa ta hanyar da'irar sarrafawa don hana ƙarfin lantarki mara sifili daga matsawa kwatsam.
Don (2) yakamata a aiwatar da hanyar aiki daidai don gujewa.
(3) Labarin gwaji ya rushe ba zato ba tsammani.Ana yawan cin karo da wannan kuma ba makawa.Idan ƙarshen ficewar na'urar ta na'ura yana da alaƙa kai tsaye da samfurin da aka gwada, lokacin da samfurin da aka gwada ya lalace ba zato ba tsammani, yiwuwar ƙarshen kanti na na'urar za ta zama sifili, wanda yayi daidai da aikin kwatsam akan kanti. Ƙarshen injin na'urar gwaji — gaban igiyar igiyar ruwa ɗaya yana da tudu matuƙa Maɗaukakin ƙimar igiyar wutar lantarki ta ƙwaƙƙwara daidai yake da ƙimar nan take na ƙarfin gwajin abin gwajin nan take, amma polarity ya saba.Wannan zai haifar da wuce gona da iri masu haɗari a kan madaidaicin insulation na iska na gwaji.
Hanyar hana shi ita ce haɗa wani resistor mai kariya tare da ƙimar juriya mai dacewa a cikin jeri tsakanin tashar wutar lantarki ƙarshen na'urar gwajin ƙarfin mitar resonance da abin gwajin, don haka ƙarfin wutar lantarki na kishiyar polarity yana aiki akan jerin da'irar da kariya resistor da kuma na'urar shigar da wutar lantarki capacitance.Na ɗan gajeren lokaci, yawancin ƙarfin lantarki yana faɗuwa a kan kariyar kariya.