GD3126A (GD3126B) Gwajin Juriya na Insulation 5kV/10TΩ (10kV/20TΩ)
GD3126A (GD3126B) Insulation Resistance Tester ana amfani dashi sosai don kiyaye kayan aikin lantarki a cikin tashar wutar lantarki, injin wutar lantarki, da sauransu. leakage current (Ix) da capacitance absorption (Cx) na kowane nau'in kayan aikin wuta mai ƙarfi, gami da switchgear, transfoma, reactors, capacitors, motors, janareta da igiyoyi, da sauransu.
●Yana ɗaukar sarrafa microcomputer, aikin menu da babban nunin ɗigon allo na LCD tare da ingantaccen aiki.
●Ƙarfin ƙarfin hana tsangwama, wanda ya dace da aunawa a cikin ƙaƙƙarfan tsangwama na lantarki.
●Babban iya aiki, na iya saduwa da buƙatun babban ƙarfin lantarki, babban juriya, babban gwajin ƙarfin ƙarfin aiki.
●Tare da ƙaƙƙarfan ƙaƙƙarfan ƙaƙƙarfan ƙaƙƙarfan ƙaƙƙarfan ƙaƙƙarfan ƙaƙƙarfan ƙaƙƙarfan ƙaƙƙarfan tsari da ƙura, daidaitawa da yanayin aiki mai tsauri.
●Abokan mai amfani, nuna ingantaccen sakamako da yanayin canjin bayanai.
●Cikakken aikin kariya, mai iya jure tasirin gajeriyar da'ira da ma'aunin wutar lantarki da aka auna.
●5 matakan fitarwa na ƙarfin lantarki na 250V, 500V, 1.0kV, 2.5kV, 5.0kV.
●6 matakan fitarwa na ƙarfin lantarki na 250V, 500V, 1.0kV, 2.5kV, 5.0kV, 10kV.Babban ƙarfin lantarki na kowane mataki yana ci gaba da daidaitawa daga sifili.
●Fitar babban ƙarfin lantarki kuma ana iya ci gaba da daidaita shi.
●Atomatik Aunawa na R15, R60, R600, atomatik lissafin sha rabo, polarization index.
●Matsakaicin ma'aunin juriya shine 0 ~ 10TΩ (0 ~ 20TΩ), kewayon sauyawa ta atomatik.
●Aunawa ta atomatik na yanayin yanayi, zafi na iska da lokacin gwaji.
●Nuna lokacin gwaji, shawarwarin buzz a kowane sakan 15, mintuna 5 ba tare da aiki ba zai sa a rufe.
●Fitar da babban ƙarfin lantarki ta atomatik bayan an gama aunawa, lokacin fitarwa bai wuce daƙiƙa 30 ba.
●Adana ƙungiyoyi 60 na sakamakon aunawa, rashin daidaituwa na shekaru 20..
●Tare da RS232 serial interface, mai ikon sadarwa tare da kwamfuta.
●Tare da firinta na waje, na iya buga sakamakon aunawa.(na zaɓi)
●Ana nuna wutar lantarki na samfurin da aka caje kafin gwaji kuma yana da alamun da suka dace.
●Lokacin gwajin da aka saita, dakatar da awo ta atomatik;
●Mai ikon gano ɗigowar Ix na yanzu da ƙarfin sha Cx.
| Matakan gwajin ƙarfin lantarki | GD3126A (5kV) GD3126B (10kV) | ||||||
| 250V, 500V, 1.0kV, 2.5kV, 5.0kV, 10kV | |||||||
| Kuskuren wutar lantarki na fitarwa | ± 5% | ||||||
| Kewayon juriya | Babban iyaka | 500GΩ~10TΩ | |||||
| Ƙananan iyaka | 0.1MΩ | ||||||
| Daidaiton aji | Darasi 5.0 | ||||||
| Kuskuren nuni mai girma | ±(5%•Ux + 1dijital) | ||||||
| Leakage na yanzu Ix na aunawa & kuskure | 0.1nA ~ 9.9mA 5% | ||||||
| Absorption capacitance Cx auna kewayon & kuskure | 0.1pF ~ 99ɥF 5% | ||||||
| Kuskuren auna zafin jiki | ± 0.5 ℃ | ||||||
| Kuskuren auna humidity | ± 2% RH | ||||||
| Short circuit current | <6mA | ||||||
| Voltage ripple | <3% | ||||||
| Lokacin gwaji | Har zuwa mintuna 99 | ||||||
| Juriya na rufi | > 500 MΩ (tsakanin gwajin waya da akwati) | ||||||
| Juriya irin ƙarfin lantarki | AC10.0kV 50Hz 1min (tsakanin gwajin waya da harka) | ||||||
| Tushen wutan lantarki | 12V baturi lithium | ||||||
| Lokacin sabis na baturi bayan caji ɗaya | 30days sau 10 DAR & 5times PI gwajin kowace rana | ||||||
| Yanayin aiki da zafi | 0 ℃ ~ + 40 ℃ <85% RH | ||||||
| Yanayin ajiya da zafi | - 20 ℃ ~ + 50 ℃ <90% RH | ||||||
| Tushen wutan lantarki | 220V AC 50Hz | ||||||
| Girma (mm) | 325 (L)*250(W)*130(H) | ||||||
| Nauyi | 3.7kg | ||||||
| Kuskuren auna juriya | |||||||
| Matakan wutar lantarki | 250 V | 500 V | 1.0 kV | 2.5 kV | 5.0 kV | 10KV | |
| ± ( 3% · Rx + 1d) | 1GΩ | 2GΩ | 4GΩ | 10GΩ | 20GΩ | 40GΩ | |
| ± ( 5% · Rx + 1d) | 10GΩ | 20GΩ | 40GΩ | 0.1TΩ | 0.2TΩ | 0.4T ku | |
| ± ( 10% · Rx + 2d) | 100GΩ | 200GΩ | 0.4T ku | 1TΩ | 2 TO | 4TΩ | |
| ± ( 25% · Rx + 2d) | 500GΩ | 1TΩ | 2TΩ | 5TΩ | 10TΩ | 20TΩ | |
| Gwajin juriya na rufi | 1 saiti |
| Gwajin haɗin kebul don tashar L (Ja) | 1 tushen (1 yanki) |
| Gwajin haɗin kebul don tashar G (Green) | 1 tushen (1 yanki) |
| Gwajin haɗin kebul don tashar E (Black) | 1 tushen (1 yanki) |
| 3Apower Adafta (Don samar da wutar lantarki da cajin kayan aiki) | 1 piece (1 guda) |
| RS232 Serial sadarwar layi | 1 tushen (1 yanki) |
| Mai amfani's jagora | 1 kwafi (1 guda) |
| Rahoton Gwaji | 1 kwafi (1 guda) |

1. L tasha soket 2. G tasha soket 3. E tasha soket 4. LCD allo
5. Buzzer 6. Zazzabi & zafi firikwensin 7. Maɓallin ESC 8. Maɓallin UP
9. Maɓallin bambanci 10. Maɓallin ƙasa 11. Maɓallin Ok12. High ƙarfin lantarki daidaita matsi
13. RS232 dubawa 14. Power switch15. Cajin soket