GD3128 Jerin Juriya Juriya
GD3128 jerin Insulation Resistance Tester yana da cikakkiyar aikin gwaji na sigogin juriya daban-daban da ingantaccen ikon tsangwama, wanda za'a iya amfani da shi don gwada juriya na juriya na babban ƙarfin ƙarfin lantarki mai ƙarfin lantarki da layin watsawa a cikin yanayi mai ƙarfi mai ƙarfi kamar substation.Kayan aiki yana ɗaukar allon taɓawa na launi na gaskiya, duk bayanan gwaji da ƙarfin baturi ana nuna su akan allo ɗaya a kallo, kuma haɗuwa da maɓallin ƙwanƙwasa da maɓallin yana sa aikin ya kasance mai sauƙi.Mai amfani baya buƙatar haddace hanyar aiki.Danna "HELP" akan allon don buɗe hanyar aiki, wanda zai iya jagorantar mai amfani yadda ya kamata don sarrafa kayan aikin.Kayan aiki yana da aikin fitarwa mai sauri, wanda zai iya fitar da wutar lantarki na abin da aka gwada nan take ba tare da ƙarin da'irar fitarwa ba.Na'urar kula da wutar lantarki na kayan aiki na iya saka idanu kai tsaye kan ƙarfin lantarki na abin da aka gwada.Idan ƙarfin lantarki ya wuce 36V, gwajin za a haramta shi ta atomatik, wanda zai iya kare kayan aiki yadda ya kamata da masu aiki.
Kayan aikin yana ɗaukar fakitin baturin lithium babba mai ƙarfi.Mai ƙidayar gwajin kayan aikin ta atomatik yana yin rikodin lokacin gwajin kuma yana adana sakamakon gwajin tare da kwanan wata da lokaci.Allon taɓawa zai iya samun sauƙin shiga bayanan tarihi da aka yi rikodi.Keɓaɓɓen keɓantaccen kebul ɗin kebul ɗin zai iya loda bayanan gwajin cikin aminci a cikin PC.Na'urar tana sanye da layin gwaji tare da rufin kariya biyu, kuma babban ƙarfin lantarki yana sanye da faifan alligator da ƙugiya mai maye gurbin, wanda zai iya dacewa da wuraren gwaji daban-daban.Kayan aiki yana ɗaukar ingantaccen tsarin harsashi mai Layer biyu, kuma matakin kariya na akwatin waje shine IP65, wanda zai iya hana mamayewa da danshi da ƙura yayin sufuri da adanawa, kuma yadda yakamata ya kare kayan aikin daga karo.
GD3128 jerin yana da fadi da kewayon, babban ƙuduri, aiki mai dacewa, sturdiness da karko, daidaito da amintacce, aikin barga, da ƙarfin hana tsangwama.Kayan aiki yana da gwajin juriya (IR);gwajin index na polarization (PI);Gwajin rabo na sha (DAR);gwajin ramp (RAMP);gwajin tacewa (FR, 10S, 20S, 30S, 40S zaɓuɓɓuka huɗu);gwajin wutar lantarki (V);gwajin ƙarfin ƙarfin (uF);gwajin halin yanzu (nA) da sauran ayyuka.Kayan aiki ya dace da gwajin juriya na kayan aiki na lantarki, layin watsawa da sauran manyan kayan aiki a ƙarƙashin yanayin babban ƙarfin, ƙarfin lantarki da ƙaddamarwa mai ƙarfi.Kayan aiki ne da aka saba amfani da shi kuma ba makawa don wutar lantarki, sadarwa, yanayin yanayi, dakin kwamfuta, filin mai, shigarwa da kulawa da lantarki, da sassan samar da wutar lantarki na masana'antu da masana'antar hakar ma'adinai.
●Matsakaicin gajeren kewayawa na yanzu shine 7mA.
●Gwajin juriya na insulation (IR), gwajin ƙididdiga na polarization (PI), gwajin rabo na sha (DAR).
●Yanayin Gwajin Ramp (RAMP), Yanayin Gwajin tacewa (FR), Gwajin iya aiki (uF)
●Ayyukan saka idanu na wutar lantarki, ta atomatik saka idanu da cajin ƙarfin abin da aka gwada.
●Aikin mai ƙididdigewa, yi rikodin lokacin gwaji ta atomatik.
●Ayyukan fitarwa ta atomatik, ta atomatik da sauri sakin cajin abin gwajin bayan gwajin, ba tare da da'irar fitarwa ta waje ba.
●Aikin kashewa ta atomatik.
●Babban allon launi taɓawa.
●Tsarin harsashi biyu-Layer, mai ƙarfi kuma mai dorewa, matakin kariya IP65.
●Fakitin baturin lithium mai ƙarfi mai ƙarfi.
●Ayyukan ajiya, na iya adana ƙungiyoyin 1000 ta atomatik na bayanan gwaji na ainihi tare da kwanan wata da lokacin gwaji da lokacin gwaji.
●Ayyukan loda, sanye take da kebul na USB, ana iya loda bayanan rikodin zuwa kwamfuta don ƙididdigar ƙididdiga na bayanai.
Samfurin Samfura | Ƙimar Wutar Lantarki | Range Resistance Insulation | Gajeren Da'irar Yanzu |
GD3128A | 250V,500V,1kV,2.5kV,5kV | 0.50MΩ ~ 10.0TΩ | ≥7mA |
Saukewa: GD3128B | 250V,500V,1kV,2.5kV,5kV, 10kV | 0.50MΩ ~ 20.0TΩ | ≥7mA |
Saukewa: GD3128C | 250V,500V,1kV,2.5kV,5kV, 10kV, 15kV | 0.50MΩ ~ 30.0TΩ | ≥7mA |
Tsawon Juriya na Insulation da Daidaitawa
Ƙimar Wutar Lantarki | Rage Resistance Insulation | Daidaito | Magana |
250V | 0.50MΩ~50.0GΩ | ± 5%rdg± 3dgt |
|
50.0GΩ~500GΩ | ± 20%rdg± 3dgt |
| |
500V | 1.00MΩ~100GΩ | ± 5%rdg± 3dgt |
|
100GΩ~1.00TΩ | ± 20%rdg± 3dgt |
| |
1000V | 1.00MΩ~200GΩ | ± 5%rdg± 3dgt |
|
200GΩ~2.00TΩ | ± 20%rdg± 3dgt |
| |
2500V | 1.00MΩ~500GΩ | ± 5%rdg± 3dgt |
|
500GΩ~3.00TΩ | ± 20%rdg± 3dgt |
| |
5000V | 1.00MΩ~1.00TΩ | ± 5%rdg± 3dgt |
|
1.00TΩ~10.0TΩ | ± 20%rdg± 3dgt |
| |
10KV | 1.00MΩ~2.00TΩ | ± 5%rdg± 3dgt |
|
2.00TΩ~20.0TΩ | ± 20%rdg± 3dgt |
| |
15KV | 1.00MΩ~3.00TΩ | ± 5%rdg± 3dgt |
|
3.00TΩ~30.0T | ± 20%rdg± 3dgt |
1 TΩ (Tera ohm)=1000GΩ=1012Ω
1 GΩ (Giga ohm)=1000MΩ=109Ω
1 MΩ (Mega ohm)=1000KΩ=106Ω
Aiki | Ma'aunin juriya (IR);Ma'auni na polarization (PI);rabon sha (DAR);Yanayin gwajin ramp (RAMP);taceaiki(10S, 20S, 30S, 40S);voltage ma'auni (V);capacitanceaunawa(uF);auna halin yanzu(nA) |
Tushen wutan lantarki | Batirin lithium mai caji 6.2Ah |
Ƙimar Wutar Lantarki | GD3128A: 250V, 500V, 1kV, 2.5kV, 5kV Saukewa: GD3128B: 250V, 500V, 1kV, 2.5kV, 5kV, 10kV Saukewa: GD3128C: 250V, 500V, 1kV, 2.5kV, 5kV, 10kV, 15kV |
Fitowar Wutar Lantarki | (5%~10%) ± 10V |
Rage Gwajin Juriya na Insulation | GD3128: 0.50MΩ~10.0TΩ Saukewa: GD3128B: 0.50MΩ~20.0TΩ Saukewa: GD3128C: 0.50MΩ~30.0T |
Fitowar Gajerun Kewayawa Yanzu | ≥7mA |
Gwajin Fihirisar Polarization | Ee |
Gwajin Rabon Sha | Ee |
Yanayin Gwajin Ramp | Gwaji cikin matakan 10% na ƙarfin lantarki da aka saita har sai an saita ƙarfin lantarki. |
Yanayin Gwajin Tace | 10S, 20S, 30S, 40S guda huɗu zaɓaɓɓu. |
Gwajin wutar lantarki | Rage: AC / DC: 0V~1000V; Daidaito: ± 5%rdg± 3V |
Gwajin iya aiki | Rage: 10 nF~25uF ku; Daidaito: ± 10%rdg± 10nF |
Gwajin Yanzu | Rage: 0.01nA~7mA ku; Daidaito: ± 5%rdg ± 0.5nA |
Mai Kula da Wutar Lantarki | Saka idanu da ƙarfin lantarki nagwajid abu, da saka idanu matsayin fitarwa bayan gwaji, an hana gwadawa lokacin da ƙarfin lantarki ya wuce 36V, kare kayan aiki da mai aiki. |
Gwaji Timer | Lokacin gwajin rikodin atomatik, lokaciingiyaka: 0s ~ 9999s |
Aikin Ajiya | Ajiye bayanan gwajin ta atomatik tare da kwanan wata da lokacin gwaji, jimlar ƙungiyoyi 1000 |
Ayyukan Loda | Loda bayanan da aka adana zuwa kwamfuta ta hanyar kebul na sadarwa. |
Nuni Wutar Batir | Tare da nunin ƙarfin baturi, lokacin da ƙarancin ƙarfin baturi zai tunatar da shicajibaturi. |
Rufewar atomatik | Bayan minti 15 farawa zai rufe ta atomatik ba tare da wani aiki ba. |
Girma | 280mm × 260mm × 160mm |
Nauyi | 4900g (har da baturi) |
Gwajin Wayoyi | Red launi high ƙarfin lantarki gwajin waya 1pc (tare daa alligator clip and ƙugiya), koren gwajin waya 1pc, baƙar fata gwajin waya 1pc |
Matsayin Kariya | Rufe shari'ar IP65, buɗe shari'ar IP40 |
Muhallin Aiki | -20 ℃~50 ℃; 80% rh |
Muhalli na Store | -25 ℃~65 ℃; 80% rh |
Juriya na Insulation | 50MΩ(1000V) (tsakanin da'irar gwaji da harsashi) |
Tsare Wuta | AC 3kV50Hz 1 min(tsakanin da'irar gwaji da harsashi) |
Tsaro | Saukewa: IEC61010-1, Saukewa: IEC61326-1 |