GDSF-311WPD 3-In-1 SF6 Gas Analyzer
GDSF-311WPD (GDSF-411WPD) kayan aiki ne mai mahimmanci lokacin da ya wajaba don gwada abun ciki na ruwa, tsabta da samfurori na SF6 gas.Babban bangaren gwajin raɓa shine jerin firikwensin DRYCAP® wanda kamfanin Finland Vaisala ya samar.Ƙa'idar infrared SF6 na'urar firikwensin gwajin gas ɗin da Kamfanin Sensor na Turai ya ƙera ana amfani da shi don gwada tsabtar iskar SF6.Na'urar firikwensin lantarki da Kamfanin Mombabo ya ƙera a Switzerland ana amfani da shi azaman abin ji don gwajin samfuran bazuwar iskar gas na SF6.Tare da kwakwalwan kwamfuta na ƙwararrun kayan aiki da ingantattun algorithms na software na STMicroelectronics, mun samar da sabon ƙarni na 3-in-1 gas analyzer.


SF6Danshi
●Hanyar aunawa: Ƙa'idar ma'aunin juriya da ƙarfi
●Ma'auni: ma'aunin raɓa -80 ℃ - + 20 ℃ (goyan bayan ppm)
●Daidaito: ± 1 ℃
(lokacin da zafin raɓa ya kasa 0 ℃, firikwensin firikwensin shine wurin sanyi)
●Lokacin amsawa: 63% [90%]
+20→-20℃ Td 5s[45s]
-20→-60℃ Td 10s[240s]
●Tsayi: 0.01 ℃
●Maimaituwa: ± 0.5 ℃
●Naúrar nuni: ℃, ppm, ℃P20 (ƙimar da aka canza a 20 ℃)
●Gudun iskar gas: 400-600ml/min
●Nuni mai gudana: 0-1000mL Mitar kwararar dijital
●Misalin matsin lamba: ≤1MPa
SF6Tsafta
●Hanyar aunawa: Ƙa'idar Auna Infrared (Na'urori masu auna firikwensin NDIR)
●Ma'auni: 0 ~ 100% SF6
●Lokacin amsawa: [90%] 60s
●Daidaito: ± 0.5% FS
●Maimaituwa: ± 0.5%
●Matsayi: 0.01%
●Naúrar nuni: %
SF6Kayayyakin Rubutu
●Hanyar aunawa: Ƙa'idar Ma'auni na Electrochemical (Electrochemical jerin firikwensin)
●Ma'auni: H2S: 0 ~ 200ppmv
SO2: 0 ~ 200ppmv
CO: 0 ~ 500ppmv
HF: 0 ~ 50ppmv
●Daidaito: H2S: 10ppmv ± 3%
SO2: 10ppmv ± 3%
CO: 50ppmv ± 4%
HF: 10ppmv ± 3%
●Maimaituwa: H2S: 10ppmv ± 2%
SO2: 10ppmv ± 2%
CO: 50ppmv ± 2%
HF: 10ppmv ± 2%
●Matsakaicin: 0.01ppmv
●Naúrar nuni: ppm
●Ƙarfin wutar lantarki: 220VAC ± 10%, 50Hz, AC / DC amfani, kariya ta caji, ci gaba da aiki ba ƙasa da 8hours ba.
●Yi amfani da yanayin zafi: -20--+60 ℃
●Yanayin muhalli: 90% RH
●Tasirin ƙimar ƙimar: Babu tasirin matsa lamba da kwarara
●Girma: 395*295*155mm
●Nauyi: kusan 2kg.
Saukewa: GDSF-411WPD SF6Kayayyakin Rubutu
●Daidaito: H2S: <10ppmv ± 0.3ppmv;> 10ppmv ± 3%
SO2: <10ppmv ± 0.3PPmv;> 10ppmv ± 3%
●Maimaituwa: H2S: <10ppmv ± 0.2ppmv;> 10ppmv ± 2%
SO2: <10ppmv ± 0.2PPmv;> 10ppmv ± 2%
●Sake amfani da aikin cikawa: sake amfani da ɗakin 2L,lokacin sake amfani da ≤ 5min
Tare da aikin bushewa gas
●Girma: 395*295*315mm
●Nauyi: kusan 5kg.
| Babban Gwaji | guda 1 |
| Adafta | 1 saita |
| Teflon bututu (gami da kwarara daidaita bawul da sauri haši) | 1 saita |
| Bututun wutsiya | 1 saita |
| Kayan kayan gyara | 1 saita |
| Caja | guda 1 |
| Mai amfani's Guide | guda 1 |
| Rahoton Gwaji | guda 1 |