Tsarin Sa ido akan Kan Layi Mai Canjawa Mai Gas Chromatography
GDDJ-DGA Transformer Oil Gas Analyzer shine na'urar sa ido kan layi don narkar da iskar gas a cikin mai taswira bisa fasahar chromatography gas.An ƙayyade kuskure mai yuwuwa, sakin faɗakarwa gwargwadon ƙimar da aka saita ta tsarin ƙwararrun bincike.
Na'urar tana ɗaukar fasahar samfurin sarrafawa da aka rarraba kuma tana da binciken kai da ayyukan dawo da kai.Kowane tsarin aiki yana da rauni haɗin gwiwa, aiki mai zaman kansa, ɗaukar tsarin tara, mai sauƙin kiyaye aikin injiniya.
●Ba tare da kulawa ba, babu buƙatar maye gurbin silinda gas.
●Gano kan-layi ƙaddamarwa da ƙimar girma na H2, CO, CO2, CH4, C2H4, C2H2, C2H6.
●Ƙirar ƙira da ƙaƙƙarfan tsari, mai sauƙi don kiyayewa, tare da haɓaka mai girma, ana iya haɗawa cikin sauƙi zuwa sauran kayan aikin saka idanu.
●Yanayin samfurin sake zagayowar ƙididdigewa, don yin la'akari da yanayin narkar da iskar gas a cikin mai.
●Pumpless injin degassing fasaha, babu bukatar injin famfo da inganta AMINCI da kwanciyar hankali na tsarin.
●Musamman hadaddun chromatographic shafi, don inganta matakin rabuwa na abun da ke ciki na gas.
●Mai gano layin layi na musamman, bayanan saka idanu na gaske ne kuma abin dogaro, sakamakon gwaji yana kusa da bayanan dakin gwaje-gwaje.
●Naúrar mai zaman kanta a cikin chassis don sarrafa zafin jiki da zafi, don cire tasirin yanki da yanayi.
●Tare da high data saye daidaici, shi rungumi dabi'ar △-ε 24 lambobi ADC da dijital tace.Yana amfani da daidaitawa ta atomatik don tattara spectrogram.
●Tare da nunin bayanai daban-daban da hanyoyin tambaya, rahoto da jadawali masu tasowa.Ana iya adana bayanan tarihi har zuwa shekaru 10.
●Ƙarfin daidaitawar muhalli mai ƙarfi, aikace-aikacen nasara a cikin sanyi, babban zafin jiki, zafi mai zafi, yanki mai tsayi.
●Ƙarfin ƙarfin hana tsangwama, daidaitawar lantarki na iya gamsar da ma'aunin da ya dace.
●Tare da matakai biyu na aikin ƙararrawa, siginar ƙararrawa za a iya watsa shi da nisa.
●Zagayowar bincike cikin sauri, mafi ƙarancin zagayowar sa ido shine mintuna 40, masu amfani za su iya saita su.
●Cikakkun fasahar dawo da mai, yayin aiwatar da aikin samar da man, samfurin mai baya tuntuɓar iskar gas ɗin chromatogram, yin amfani da hanyoyi daban-daban na sarrafawa, don tabbatar da cewa jikin mai canzawa na samfurin mai ya cika cikakkiyar buƙatun.
●Ƙarfafa tsarin ganewar asali, ana ba da sakamako ta hanyar ingantacciyar hanyar rabo uku, hanyar David triangle da hanyar zane mai siffar cube.
●Tare da hanyoyin sadarwa daban-daban don canja wurin bayanai, ana amfani da RS485, IEC61850, canja wurin mara waya ta GPRS da gajeriyar saƙo don canja wurin bayanai.
●Goyan bayan Ethernet/hanyar gani, canja wurin bayanai, sarrafa na'ura da saitin siga tare da cikakken ƙididdigewa da sarrafa nesa.
●Akwai aikin gyaran mota na mai/gas da ayyukan tsaftacewa ta atomatik.
| Yanayin yanayi | -40 ℃~+70 ℃ | ||
| Yanayin muhalli | Dangantakar zafi 5-95% (babu tari) | ||
| Matsin yanayi | 80kPa-110kPa | ||
| Tushen wutan lantarki | AC 220V± 10%, 50Hz | ||
| Abubuwan sa ido | H2, CO, CO2, CH4, C2H4, C2H2, C2H6, H2O, girman girma da maida hankali | ||
| Analysis da aikin bincike | Bincika da tantance bayanan sa ido ta hanyar ragi uku, hanyar David triangle da hanyar zane mai siffar cube.Za a iya ba da spectrogram na asali. | ||
| Min.Zagayen ganowa | 40-60mins, an ayyana mai amfani, tsoho sau huɗu a rana. | ||
| Yanayin samfur | Samfurin kekuna, don nuna ainihin yanayin halin da ake ciki na gas. | ||
| Yanayin raba mai da iskar gas | Vacuum degassing yanayin, degassing har sau uku ci gaba. | ||
| Rayuwar ajiyar bayanai | ≥ shekaru 10 | ||
| Yawan iskar gas | Gas mai ɗaukar kaya da kansa, ba a katse shi duk shekara.Babu buƙatar maye gurbin silinda gas. | ||
| Kula da iskar gas | Ma'auni kewayon | Min.ganowa | Kuskure |
| H2 | 2-2000 ppm | 1 ppm | ± 10% |
| CO | 5-20000 ppm | 5ppm ku | ± 10% |
| CH4 | 0.2-2000 ppm | 0.2 ppm | ± 10% |
| C2H4 | 0.2-2000 ppm | 0.2 ppm | ± 10% |
| C2H6 | 0.2-2000 ppm | 0.2 ppm | ± 10% |
| C2H2 | 0.2-2000 ppm | 0.2 ppm | ± 10% |
| CO2 | 25-20000 ppm | 25ppm ku | ± 10% |
| H2O | 1 - 800 ppm | ||
| Yanayin mai | -40 ℃ ~ 200 ℃ | ||
| Jimlar yawan iska | 0.2-15% | ||
| Jimlar hydrocarbon | 1-8000 ppm | ||
| Kwanciyar hankali (kuskuren aunawa) | A daidai wannan yanayin gwaji, kuskuren bai wuce 10% ba don samfurin mai iri ɗaya.(matsakaicin maida hankali) | ||
| IP class | IP66 | ||
| Tsayi | ≤3000m |
| Yanayin yanayi | -10 ℃ ~ + 45 ℃ (a cikin gida);-40 ℃ ~ + 70 ℃ (waje) |
| Max.bambancin yanayin zafi na yau da kullun | 25 ℃ |
| Max.dangi zafi | 95% (matsakaicin yau da kullun);90% (matsakaicin wata-wata) |
| Matsin iska | 86kPa ~ 106kPa |
| Anti-shock iyawar | Hanzarta a kwance 0.30g;a tsaye hanzari 0.15g |
| Yanayin shigarwa | Shigarwa na cikin gida.Dakin za a sanye shi da na'urar sanyaya iska, babu garkuwa, ba tare da matakan kariya ba. |
| Ƙimar wutar lantarki (AC) | 220V/100V, kuskuren halatta ± 20% (harmonics), jimlar karkatar da wutar lantarki ≤8%. |
| Ƙimar wutar lantarki (DC) | 220V/110V, halattaccen kewayon bambancin ± 20%. |
| Ƙarfin wutar lantarki na AC | 57.7V / 100V / 220V, obalodi iya aiki ne 1.2times na rated irin ƙarfin lantarki, ganiya coefficient ≥2. |
| rated AC halin yanzu | 1A/5A, iya aiki mai yawa shine sau 1.2 na rated halin yanzu, ci gaba da aiki, mafi girman coefficient ≥3. |
| Ƙididdigar mita | 50Hz, kuskuren halatta -5% ~+5%. |
Tushen wutan lantarki
Ya kamata samar da wutar lantarki na tsarin sa ido kan yanayin tashar tashar ya kasance mai aminci kuma abin dogaro, kuma kayan aikin Layer na tashar ya kamata a yi amfani da wutar lantarki ta 220VAC marar katsewa (UPS).Kowace naúrar sa ido a cikin tsarin aikin ana samun ƙarfi ta tsarin 220V AC.
Kariyar walƙiya, ƙasa, hana tsangwama
Tsarin sa ido kan yanayin tashar tashar zai sami matakan kariya daga wuce gona da iri.
Babu keɓantaccen grid na ƙasa don tsarin lura da yanayin.Bisa ga ka'idar "ƙasa mai maki ɗaya", ana haɗa wayar ƙasa zuwa aya ɗaya na babban grid na ƙasa na tashar.
Za a shigar da na'urar kariya fiye da ƙarfin lantarki akan 220V AC samar da wutar lantarki, layin sadarwa da jagorar ƙarshen cibiyar sadarwar ƙasa, kuma sigogin na'urar kariya za su dace da ma'aunin aikin rufewa na kayan aiki.
Ya kamata a yi ƙasa a dogara da ƙaƙƙarfan shassis, majalisar da kebul na kariya na tsarin kula da yanayin.Haɗin kai tsakanin matakan tsari na tsarin kula da yanayin yanayin, haɗin kai tsakanin tsarin aiki da tashar kula da tashar, da haɗin kai tsakanin tashoshin sadarwa na kayan aiki dole ne a ware.
An shigar da na'urar a cikin daki ba tare da kariya ta lantarki ba.Na'urar kanta yakamata ta cika buƙatun kutsawa cikin filin anti-electromagnetic da tasirin electrostatic.Idan akwai ƙarfin walƙiya, yawan ƙarfin aiki da kuskuren gajeriyar hanya na kayan aikin farko, kayan aikin ba za su yi aiki da kyau ba, kuma duk kayan aikin za su cika waɗannan buƙatun hana tsangwama:
1) Don fitarwar lantarki, ya dace da GB/T 17626-4-2 aji 4.
2) Don filin lantarki na radiation, ya dace da GB/T 17626-4-3 class 3.
3) Don saurin wucewa, ya dace da GB/T 17626-4-4 aji 4.
4) Don karuwa, ya dace da GB/T 17626-4-5 aji 3.
5) Don gudanar da shigarwar lantarki, ya dace da GB/T 17626-4-6 aji 3.
6) Don filin lantarki na mitar wutar lantarki, ya dace da GB/T 17626-4-8 aji 4.
7) Don filin lantarki na bugun jini, ya dace da GB/T 17626-4-9 aji 5.
8) Domin damped oscillating Magnetic filin, ya dace da GB/T 17626-4-10 class 5.
9) Don raƙuman motsi, ya dace da GB/T 17626-4-12 aji 2 (tashar siginar).
| A'a. | Sunan Kayan aiki | Ƙayyadaddun bayanai | Qty | Magana |
| 1 | Tsarin sa ido akan Mai Transformer Oil Gas Online | 535*600*1100 | 1 | |
| 2 | Flange | Dangane da tashar wutar lantarki | 2 | |
| 3 | Bakin karfe tube | Φ6*30M | 1 | |
| 4 | Fiber na gani | Multimode 4-core, 200M | 1 | |
| 5 | Akwatin tashar | 2 | ||
| 6 | Jumper | SC-SC | 2 | |
| 7 | Fiber Converter | multimode | 1 | |
| 8 | kebul na Ethernet | 0.5M | 2 | |
| 9 | Dunƙule | M12*1.25M, Φ6 | 2 | |
| 10 | Fadada dunƙule | M10*100 | 4 | |
| 11 | Makullin majalisar | 2pcs | 1 | |
| 12 | Katin kebul | 4pcs+ da dama na nailan na igiyoyi | 1 | |
| 13 | Bakin karfe tube | Φ3*2M | 1 | |
| 14 | Insulation Pipe da sauran abubuwan da aka gyara | Insulation bututu Φ6 * 2M 4pcs, Au tef 50*25M 1roll, bakin karfe hoop 8*32 2pcs | 1 |